Automation and malfunctions of Bosch Gaz 6000 W boilers

Automatic control for gas boilers Bosch Gaz 6000 W

The control panel of Bosch 6000 W gas convection boilers with the Cotronic 3 data bus allows you to control the heating system depending on the room temperature.

For these wall-mounted convection gas boilers, two types of Bosch regulators are recommended.

Programmable room temperature controller OpenThermTM CR12005

Rice. 7. Combination of a programmable room temperature controller OpenThermTM CR12005 with the control panel of a Bosch 6000 gas convection boiler

Purpose and functions:

OpenThermTM programmable thermostat for boiler control with Cotronic 3 data bus.

Data exchange with the controller via a two-wire bus.

Two-wire bus technology, reverse polarity protection.

Simple, intuitive settings for temperature regulation and cooking control hot water.

Preset weekly programs with six switching points.

Possibility of manually changing the program for each day of the week.

LCD display with digital and graphic display of work status. Display of the current heating and domestic hot water temperature, outside temperature

(only if there is a temperature sensor), indication of the boiler burner operation status and error codes.

Possibility of remotely resetting the boiler error.

Using the OpenThermTM protocol.

The air temperature setting range in the control room is 7...39 ° C with an adjustment step of 0.5 ° C.

Room temperature controller TRZ 12-2

Fig.8. Combination of room temperature regulator TRZ 12-2 (on/off) with control panel of a gas convection boiler Bosch Gaz 6000 W

Description and functions of the controller

The room temperature regulator TRZ 12-2 is recommended for two-position regulation of the burner flame and control of the circulation pump of gas wall-mounted boilers.

Weekly programming of time intervals.

Three operating modes: “Normal”, “Economical”, “Automatic”.

Vacation function (up to 99 days).

Display of date and current time, automatic change of summer/winter time (synchronization with the system).

The room temperature adjustment range is from +5 to +39 °C.

Faults shown on the display of Bosch 6000 boilers

A7 - Hot water temperature sensor is faulty.

Check for damage or short circuit temperature sensor and its wires, replace if necessary.

Ad - Not recognized temperature sensor boiler

Check the boiler temperature sensor and connecting wire

C1- Low frequency fan rotation.

Check the mains voltage.

C4 - The differential pressure switch does not open when the fan is turned off.

Check the differential pressure switch.

C6 - The differential pressure switch does not close.

Check differential pressure switch and drain pipes flue gases.

C7 - The fan does not work.

Check the fan and its wire with plug, replace if necessary.

CE - Insufficient filling pressure of the heating system.

Add water.

d7 - Gas fittings are faulty wall-mounted boiler Bosch Gaz 6000 W.

Check the connecting wire.

E2 - Flow temperature sensor is faulty (break).

Check for damage or short circuit to the temperature sensor and its wire, replace if necessary.

E9 - The heat exchanger temperature limiter has tripped.

Check for damage to the heat exchanger temperature limiter and its connecting wire, replace if necessary.

Check operating pressure in the heating system.

Check the temperature limiter, replace if necessary.

Check the pump starting, replace the pump if necessary.

Check the fuse, replace if necessary.

Remove air from the Bosch 6000 W boiler.

Check the water circuit of the heat exchanger, replace if necessary.

Check for damage to the flue gas temperature limiter and its connecting wire, replace if necessary.

EA - No flame detected.

Check the protective conductor connection.

Check if it is open gas tap.

Check the gas supply pressure and correct if necessary.

Check the electrical connection.

Check the electrodes with wires, replace if necessary.

Check the flue gas system and clean or repair if necessary.

Check gas adjustment and correct if necessary.

For natural gas: Check the gas flow control relay, replace if necessary.

When working with combustion air taken from the room, check the air supply to the room and the ventilation openings.

Clean the heat exchanger.

Check the gas fittings, replace if necessary.

__________________________________________________________________________

__________________________________________________________________________

__________________________________________________________________________

__________________________________________________________________________

_______________________________________________________________________________

__________________________________________________________________________

OPERATION AND REPAIR OF BOILERS

Protherm Panther Protherm Stingray Protherm Bear Protherm Cheetah Evan
Ariston Egis Teplodar Cooper Atem Zhitomir Neva Lux Arderia Nova
Termona Immergas Electrolux Conord Lemax Galan Mora Aton

_______________________________________________________________________________


Gas wall mounted Buderus boilers
Models Logamax U042, U044, GB072, GB172. With open and closed camera combustion. Methods of repair and service, adjustment of operating parameters. Maintenance recommendations.
Gas heating boilers Vaillant
Models: floor-standing Atmovit exclusiv, wall-mounted condensing Ecotec plus. Service, Maintenance, settings of functional components. Hydraulic diagrams.
Gas wall mounted Ariston boilers
Models Clas, Clas Evo, Genus. Recommendations for repair, maintenance and service. Elimination of errors and malfunctions. Setting and adjustment methods.
Gas boilers Immergaz
Models Eolo Star, Eolo Mini, Nike Star, Nike Mini, Mithos. Repairs and adjustments. Installation, assembly and connection. Operating mode settings and additional equipment.
Boilers Kentatsu Furst
Wall models Nobby Smart. Condensing Smart Condens. Floor standing Sigma, Kobold. Solid fuel Elegant, Vulkan. Malfunctions and error codes. Description and characteristics.


Bosch boiler - Errors and their meaning

Error codes for Bosch WBN 6000 boilers

A7- Malfunction of the DHW temperature sensor. Inspect the sensor for defects or short circuits and its wiring. Replace if necessary.

Ad- The unit cannot detect the boiler temperature sensor.

It is necessary to inspect the boiler temperature sensor and connecting wires. C1

- The fan rotates at low speed. You need to check the mains voltage. Also inspect the flue gas exhaust system and, if necessary, clean or repair it. C4

- The differential pressure switch does not open if the fan is turned off. The differential needs to be inspected. pressure switch. C6

- The differential pressure switch does not close. Check the fan and wires with plugs. Replace if necessary. Inspect the differential. pressure switch and exhaust pipes for combustion products. C7

- The fan does not work. Check the fan and its wires with plugs. Replace if necessary. C.E.

- There is not enough pressure in the heating system. Needs to be filled with water.- Malfunction gas system. Check the connecting wire. Inspect the gas system and replace if necessary.

E2- Faulty temperature sensor on the supply line (break). Needs to be checked for possible damage or short circuit of the sensor and its wiring. Replace if necessary.

E9- The temperature limiter in the heat exchanger is triggered. It is necessary to check for possible damage to the heat exchanger temperature limiter and its connecting wires. Replace if necessary. Check the nominal pressure in the system. Inspect the temperature limiter and replace it with a new one if necessary. Check the start of the circulation pump and, if necessary, replace it. Check fuses, replace if necessary. Remove air from the unit. Check the water circuit in the heat exchanger. Replace if necessary. Check the flue gas temperature limiter for possible damage.

EA- There is no flame. Check the connection of the protection wires. Check to see if the gas valve is open. Check the gas supply pressure readings and correct if necessary. Check the connection to electrical network, electrodes with wires and, if necessary, replace. Inspect the output system combustion products, clean or repair. Check the gas adjustment,
eliminate if necessary. For natural gas: Inspect the relay that controls gas flow. Change if necessary. When working with combustion air intake from the room, check the air flow into the room and the ventilation openings. Clean the heat exchanger.

Check the gas system, replace if necessary. F7

- When switched off, the boiler detects a flame. Check for oxidation of the electrodes and replace if necessary. Inspect the combustion products exhaust system and, if necessary, clean or repair. Check the electronic control board for moisture, dry if necessary.

F.A.- Flame detected when gas supply is turned off. Check the gas system, replace if necessary. Inspect the electrodes and connecting wires, replace if necessary. Inspect the combustion product exhaust system, clean or repair it.

P

- The boiler type is not determined. Set the unit type.

Fd- Exit of flue gases at the combustion chamber. Check the heat exchanger for blockages.

A3- The flue gas temperature sensor is not defined. It is necessary to check the sensor and connecting cables for damage.

A4- Flue gas outlet at the flow fuse. Check the flue gas outlet.

A6- The temperature sensor in the combustion chamber is not detected. It is necessary to check the sensor and connecting cables for damage.

A7- Malfunction of the hot water supply (DHW) temperature sensor.

Carry out a check to look for defects or short circuits in the temperature sensor and its wiring, if necessary, replace it. A8

- Contact with the BUS bus has been interrupted. Check the contact cable and regulators. A9

- Incorrect installation of the DHW sensor. Check the mounting distances, remove the sensor if necessary and reinstall it using heat-conducting paste. A.C. - The module is not defined. The module is not connected correctly. Check the module, outside temperature sensor, remote control

Ad and contacts.

- The unit cannot detect the boiler temperature sensor. It is necessary to inspect the boiler temperature sensor and wire contacts. b1- Coding plug not defined. Conduct

correct installation coding plug, measure it and replace it if necessary.

C1, C6- The differential pressure switch does not close.

Check the fan and wires with plugs. Replace if necessary. Inspect the differential. pressure switch and exhaust pipes for combustion products. C4 - Diff. The pressure switch does not open in the off position. Check the differential pressure switch.

CC- The control unit cannot detect the outside temperature sensor.

It is necessary to inspect the sensor and contact cable

for a break. d3

E2- Jumper 161 was not detected on ST8. If there is a jumper, insert the plug correctly and check the external limiter. Otherwise: check if there is a jumper.

E9 d4 - There is a large temperature difference. Check the circulation pump, bypass hose and system pressure., remove air from the unit.

E.A.- No flame detected. Inspect the gas valve. Check the pressure in the gas network, the network connection, the ignition electrode with the wire and the ionization electrode with the cable.

F0- Internal problem. Check the correct connection of the electrical plug contacts and start lines, and if necessary, replace the electronic board.

Check the gas system, replace if necessary.- The flame is detected when the unit is turned off. Check electrodes and cables. The flue gas removal system may be faulty. Check the control board for moisture.

- When switched off, the boiler detects a flame. Check for oxidation of the electrodes and replace if necessary.- Flame detection after gas supply is turned off. Inspect the ionization electrode. Check the gas system.

P- Incorrect button press (duration more than 30 seconds).

Press the button again in less than 30 seconds.

Malfunctions and adjustments of Bosch boilers

Wall-mounted boiler Wbn 6000-24. Gas is natural. The EA error has been appearing for a very long time now. After reading about the EA error, I decided to find out the board firmware and fan stage settings. If the software version in the menu shows “245-03” and does not seem to raise any questions, then the fan stage menu shows the number “17”. The chimney system is horizontal with a concentric pipe.

The exit from the boiler is about 2 meters. I have not installed any adapter for air intake from inside the room and air enters the unit from outside the room. What guided the masters when installing the 17th fan stage, although, judging by the instructions, the 2nd stage is needed. Do I need to change the board? No adapter needed. You have a standard coax with air intake from outside. It helps to get rid of this error by setting the fan stage to 5. I had the same thing, and when I set it to 5, there has been no error for a year now. Heat exchangers recently cleaned
gas boiler

I had a similar experience. There was air in the system and after operation of the device the air came out and the pressure dropped. Is your automatic air vent valve (on top of the pump) not closed? It needs to be always open. It is better to bring the pressure to 2 atm, so that expansion tank I also took the volume in the boiler and compensated for the escaping air. In radiators, of course, you should also bleed air using a Mayevsky valve.

The Bosch 6000 24 kW gas wall-mounted boiler often gives an EA error and often turns on and off. That is, conditionally - set it to at least 40 degrees, literally 5 minutes and turned off, etc. Previously, it heated as it should, but now the first batteries are hot, the distant ones are barely warm, it doesn’t reach them.

It operates based on the return temperature; there is no room thermostat.

___________________________________________________________________________________________

___________________________________________________________________________________________

Error EA can be eliminated by setting the fan stage to value 5. The fact that the unit turns off quickly means that its minimum power is too high for your system. It cannot produce less than 8 kW. And you apparently have 5 radiators in the system. So he heats this water and turns off. And why does it heat them up so quickly? The following malfunctions are possible: something is clogged or airy, or the first radiators need to be balanced so that the entire flow does not go only through them. Here you need to look at the radiator diagram and so on. Try setting the pump speed to maximum (value 3) and bleeding air into the radiators.
Borino, ZhMZ, Siberia, Alfa Kalor, Termotechnik.

Adjustment of gas automatic equipment Eurosit 630. Replacement of thermocouple and maintenance of pilot burner.

Models Luna, Luna 3 Comfort, Luna Duo Tec (F/Fi).
Double-circuit, turbocharged. Recommendations for eliminating errors and malfunctions.

Settings and adjustment of operating modes.
Models ZWC, ZSA, ZSC, ZWR, Gaz 5000, Gaz 3000 W ZW, WBN 6000.

Wall-mounted, double-circuit. Repairs, adjustments and malfunctions.

We have such a problem. It's a Bosch double boiler, we've only been using it for six months. We turned on the hot water, but it doesn’t heat up, the boiler knocks out and shows error E9. The filter was cleaned, the device started up, but an hour later it turned off again. Shows an error. When we start it up, the pressure immediately rises and the unit shuts down. Then we turn it on, the fuses immediately burn out and the boiler goes out. We still can’t turn it on. Please help me in
what could be the reason?

Most likely your pump is jammed. Usually the fuses blow because of the pump.

Bosch gas 6000w boiler. Was purchased in August of this year. When the cold snap set in, it turned off and showed error C6 (the differential pressure switch does not turn on). After removing the front cover, it was discovered that the tubes that go to this relay were covered with frost. After drying the tubes, the device started up. This situation has been repeated several times already. Is there any way
get rid of this problem?

You need to look at how the smoke removal system is made. A separate system often leads to such consequences. We recommend replacing it with coaxial. If it is not possible to change the chimney, then the pipes need to be insulated.

Wall-mounted boiler Wbn 6000-24. Gas is natural. The EA error has been appearing for a very long time now. After reading about the EA error, I decided to find out the board firmware and fan stage settings. If the software version in the menu shows “245-03” and does not seem to raise any questions, then the fan stage menu shows the number “17”. The chimney system is horizontal with a concentric pipe. The exit from the boiler is about 2 meters. No fence adapter
I have not installed air from inside the room and air enters the unit from outside the room. What guided the masters when installing the 17th fan stage, although, judging by the instructions, the 2nd stage is needed.

Do I need to change the board?

No adapter needed. You have a standard coax with air intake from outside. It helps to get rid of this error by setting the fan stage to 5. I had the same thing, and when I set it to 5, there has been no error for a year now.

When the coolant temperature approaches the set modulation, the boiler turns on in any case, regardless of whether there is a thermostat or not, but since this process takes little time it is difficult to fix. If an OT thermostat is used, modulations begin to occur when the room temperature approaches the set temperature.

If the thermostat is set to “On/Off”, then there is no connection.
Private house 70m2 300mm foam block 50mm mineral wool and facing with ceramic bricks. There are plans to expand the area by another 50-60 square meters. m. On the ground floor, a 33m2 heating substation is installed, heating radiators are installed on both floors. DHW is provided by the kitchen and bathroom; in the future there will be a second bathroom. I want to install BKN Drazice 125. Since my house has a riser installed, I plan to install a wall-mounted gas boiler with coaxial chimney . Considering different variants . The most optimal for the price is the Bosch 6000 (18 kW), but the bosch gaz 7000 has a minimum power of 24 kW, which, I think, is too much for me. What is important is that I need the boiler to be able to set the temperature in the boiler and, in the future, it would be possible to install a room thermostat and
street sensor

. Interested

Error codes for Bosch WBN 6000 boilers

Is the difference between the indicated models in the composition of components or in the place of assembly? Maybe there are some other fundamental differences? In your case, the most optimal model will be bosch gaz wbn6000-18 and wstb 120.

Error A7- The unit cannot detect the boiler temperature sensor.

- Malfunction of the DHW temperature sensor. Inspect the sensor for defects or short circuits and its wiring. Replace if necessary. Ad Error

Error C1 C4

- The fan rotates at low speed. You need to check the mains voltage. Also inspect the flue gas exhaust system and, if necessary, clean or repair it. coding plug, measure it and replace it if necessary.

Error C4 Error C6

Error C7- The fan does not work. Check the fan and its wires with plugs. Replace if necessary.

CE error- There is not enough pressure in the heating system. Needs to be filled with water.

Error d7- Gas system malfunction. Check the connecting wire. Inspect the gas system and replace if necessary.

Error E2- The temperature limiter in the heat exchanger is triggered.
It is necessary to check for possible damage to the heat exchanger temperature limiter and its connecting wires. Replace if necessary. Check the nominal pressure in the system.

Inspect the temperature limiter and replace it with a new one if necessary. Check the start of the circulation pump and, if

it is necessary to replace it. Check fuses, replace if necessary. Remove air from the unit. Check the water circuit in the heat exchanger. Replace if necessary. Check the flue gas temperature limiter for possible damage. EA error

- There is no flame. Check the connection of the protection wires. Check to see if the gas valve is open. Check the gas supply pressure readings and correct if necessary. Check the connection to the electrical network, electrodes with wires and, if necessary, replace. Inspect the combustion product exhaust system, clean or repair it. Check the gas adjustment and correct if necessary. For natural gas: Inspect the relay that controls gas flow. Change if necessary. When working with combustion air intake from the room, check the air flow into the room and the ventilation openings. Clean the heat exchanger. Check the gas system, replace if necessary.

Error F7- Flame detected when gas supply is turned off. Check the gas system, replace if necessary. Inspect the electrodes and connecting wires, replace if necessary. Inspect the combustion product exhaust system, clean or repair it.

- When switched off, the boiler detects a flame. Check for oxidation of the electrodes and replace if necessary. Inspect the combustion products exhaust system and, if necessary, clean or repair. Check the electronic control board for moisture, dry if necessary.

- The boiler type is not determined. Set the unit type.

FA error- Exit of flue gases at the combustion chamber. Check the heat exchanger for blockages.

- Flame detected when gas supply is turned off.- The flue gas temperature sensor is not defined. It is necessary to check the sensor and connecting cables for damage.

Check the gas system, replace if necessary. Inspect the electrodes and connecting wires, replace if necessary.- Flue gas outlet at the flow fuse. Check the flue gas outlet.

Inspect the combustion product exhaust system, clean or repair it. Error P

Error Fd- Malfunction of the hot water supply (DHW) temperature sensor.

Code A2, C3 Code A3

Code A4 Code A6

- The temperature sensor in the combustion chamber is not detected. It is necessary to check the sensor and connecting cables for damage.- The module is not defined. The module is not connected correctly. Check the module, outside temperature sensor, remote control and contacts.

Code Ad and contacts.

Code b1- Coding plug not defined. Correctly install the coding plug, measure it and replace it if necessary.

Codes C1, C6- The differential pressure switch does not close.

Check the fan and wires with plugs. Replace if necessary. Inspect the differential. pressure switch and exhaust pipes for combustion products.- The differential pressure switch does not close.

Code C4 Code CC

- The control unit cannot detect the outside temperature sensor. It is necessary to inspect the sensor and contact cable for breaks. Code d3

- Jumper 161 was not detected on ST8. If there is a jumper, insert the plug correctly and check the external limiter. Otherwise: check if there is a jumper. Code d4

- There is a large temperature difference. Check the circulation pump, bypass hose and system pressure. Code d5

- The external temperature sensor is damaged. Check the sensor and connecting contacts.- Jumper 161 was not detected on ST8. If there is a jumper, insert the plug correctly and check the external limiter. Otherwise: check if there is a jumper.

Code E2 Code E9

- A limiter has tripped in the supply line. Check the pressure in the system and temperature sensors. Check the functions of the pumps and the fuse on the control board, and remove air from the unit.

EA code- No flame detected. Inspect the gas valve. Check the pressure in the gas network, the network connection, the ignition electrode with the wire and the ionization electrode with the cable.

Code F0- The flame is detected when the unit is turned off. Check electrodes and cables. The flue gas removal system may be faulty. Check the control board for moisture.

- Internal problem. Check the correct connection of the electrical plug contacts and start lines, and if necessary, replace the electronic board.- Flame detection after gas supply is turned off. Inspect the ionization electrode. Check the gas system.

Code F7 FA code

Press the button again in less than 30 seconds.

Code Fd - Incorrect button press (duration more than 30 seconds). Press the button again in less than 30 seconds. The Bosch company assures that its heat exchangers are not covered with special protective anti-corrosion paint. Heat exchangers from other companies (Viessmann, Vaillant, Ariston, Baxi) have protective layer, and they have it

pure copper

. And they present this as an advantage of their models. Is this true or is it just a reduction in the cost of the device.. The second, through the hydraulic separator. In both cases, it is used as a consumer for the heating system; accordingly, it will be heated by the temperature of the heating system. This is clear to me. But I don’t understand what I should do with the DHW taps, and whether it’s possible to just put plugs on them. At first I
I assumed that I would buy a Bosch 6000 single-circuit boiler, but since it was not available, I was recommended to opt for a double-circuit one. And I’m wondering if I plug the outlets, won’t the heat exchanger be damaged (won’t it burn out without water)? Since I will not keep the unit constantly operating at maximum, let the BKN continue to work. Moreover, I bought an ACV Comfort 130, and by design it is a tank in a tank and, in fact, should hold the temperature better than with a coil. Among the disadvantages of such boilers is the maximum pressure of 3 bar, and safety valve on the same pressure. A knowledgeable people they report that if the valve does not work for some reason, the tank will burst. About

dual-circuit model

- I am afraid that if the boiler fails, I will be left without hot water at all. Your conclusions are only valid for purified water. For domestic needs, you can set up a backup line. But in my memory, there have never been any cases of failure of ACV boilers. I organize in a private house separate smoke removal for a 24 kW Bosch 6000 gas boiler. In this regard, I have two questions.
Exhaust tract. Is it worth switching from “pants” 80-80 through a tee with a condensate drain to a vertical chimney diameter of 100 mm? Pipe cost different diameters not very different from each other. The height of the chimney to the tee is 4800 mm. I bring the pipe through the roof,
considering 10 degrees. Intake tract. I am going to organize the air intake in an unheated and well-ventilated attic. Before outer wall about 4 meters. Do not take air from the room good decision
water register with a diameter of 300-500mm). Organize circulation in the register with a separate circuit. This is very difficult, but it should give results.
Can you tell me which chimney kit is suitable for installation on the wbn 6000-24 c? You need to take the chimney out just beyond the 375 mm thick wall; you won’t need to extend it anywhere further. Since the prices for branded equipment are very high, I would like to try another manufacturer.

Neva, for example. Will it be possible to reprogram a single-circuit unit if you first turn off the DHW flow sensor?

No. It will be necessary to replace the control board of the single-circuit boiler and the hydraulic unit from it. And also install a three-way valve additionally.
We recently washed the heat exchangers of a Bosch 6000 gas boiler. It worked for a month and kept the pressure at 1 all the time. Then I noticed a strange gurgling sound inside it before the burner ignited (in cooling mode), as if water was being poured from one mug to another. I looked, and the pressure was 0. In theory, it should have automatically turned off when the pressure in the system dropped to 0.5, but it worked and warmed up the batteries.
gas boiler

The only thing was that there was a different sound and murmur. I increased the pressure to 1, but the next day the pressure dropped back to 0.5 (meaning there is a water leak somewhere). I checked the pipes and radiators, but couldn't find any leaks anywhere. The unit also does not drip, but the pressure still drops.

The Bosch 6000 24 kW gas wall-mounted boiler often gives an EA error and often turns on and off. That is, conditionally - set it to at least 40 degrees, literally 5 minutes and turned off, etc. Previously, it heated as it should, but now the first batteries are hot, the distant ones are barely warm, it doesn’t reach them.

Tell me what it could be

Tell me, who knows about: Wall-mounted gas boiler WBN 6000-18C RN. What tests are carried out in production? Do they launch them?

Everything was fine for me, I don’t think it was like this from the factory, most likely the storage was strange.

Tell me: the Bosch wall-mounted boiler stopped, the pressure rose to 3 bar, and it showed error E9r. Tried to restart it worked, after 10 seconds. The pressure jumped to the maximum, I stopped everything, turned it off, and released the pressure. I checked the gas pressure and it was normal. What could it be?

If the system is new, then the expansion tank is small, if it is old, then the expansion tank is faulty, or maybe the make-up is leaking. In your case the problem is expansion tank the most likely. If this is the case, then option 2: pump up the pressure, replace the tank.

After opening the hot water tap and igniting the burner, the Bosch boiler displays error E2 (flow temperature sensor is faulty). This happens in 10-15 seconds. After closing the tap, the error clears itself and the boiler continues to operate in heating mode. If the tap is opened again, the situation repeats. To complete the picture: An additional circulation pump, before installing it
The boiler showed error E2 in heating mode for a couple of seconds, and then changed to E9 (the heat exchanger temperature limiter tripped). Source of water supply borehole pump (water supply pressure from 2x to 3x without).

sharp jumps Possible reasons such: the own circulation pump is faulty (if it is only used in DHW mode), clogged strainer

. The sensor probably shouldn't be ruled out.

Boiler zwa 24. The concept has changed, a heat exchanger from zsa, a boiler sensor and a three-way valve are needed. The pay, I think, is the same for them. In general, from a double-circuit one it is necessary to make a single-circuit one.

__________________________________________________________________________

__________________________________________________________________________

__________________________________________________________________________

__________________________________________________________________________

_______________________________________________________________________________

The manufacturer does not recommend such modifications. But if you want, you need to purchase a heat exchanger. Their feed tubes are the same, but their outlet tubes are different. The 2-circuit one has a hole for refilling, but the 1-circuit one does not. There are 2 options. Change the handset.

Figure out how to plug the hole. The control boards are the same.

The dual-circuit device is the most popular among users. It simultaneously works for hot water supply (DHW) and heating. Some models are equipped with two heat exchangers, which provide uninterrupted operation systems.

The control panel contains power regulators. Therefore, heating can be adjusted to the area of ​​the room. How does equipment switch from one circuit to another? A three-way valve is provided for this purpose. The boiler's operation is focused on the main circuit - the heating circuit. When the mixer is opened, the valve switches the flow to the DHW system.

The circulation of the coolant is ensured by a pump. Sensors monitor the device and, in case of deviations in operation, send a signal to the control module. As a result, error codes appear.

Errors and malfunctions

The table contains error codes that correspond to models Bosch WBN 6000-24C, Bosch ZSC 24-3 (35-3) MFA, ZWC 24-3 (28-3, 35-3) MFA, Bosch ZWE 24-4 (28-3) 4), ZSE 24-4 MFA, Bosch ZWE 24-5 MFK, Bosch ZWE 24-4 (ZSE) MF.

Error code What does it mean How to fix it yourself
A2 The combustion chamber smokes. The heat exchanger is clogged with soot and scale. Clean the radiator. Remove soot with a brush. Scale is removed with reagents or a solution of citric acid.
A3 There is no signal from the flue gas sensor. Inspect the sensor wiring, tighten the contacts. Replace the faulty part.
A4 Carbon monoxide is released to the flow fuse. Clean the pipes and chimney from blockages with soot, debris, and foreign objects. Make sure there is traction.
A6 There is no contact with the burner temperature sensor. Carry out diagnostics of the connections and the sensor itself.
A7 The water thermistor has failed.
A8 There is no contact with the BUS bus. Tighten the connections from the bus to the control module. Replace cable
A9 Incorrect connection of the DHW temperature sensor. Check for incorrect connection. Install the element correctly using heat-conducting paste.
AC The module is not recognized. Inspect the wiring between the module and the display, information panel. As well as connections, outdoor thermometer.
Ad There is no connection to the water heater thermistor. Perform diagnostics of all contacts and sensor.
- The unit cannot detect the boiler temperature sensor. The system does not find the coding plug.
  • Insert the plug firmly into the socket.
  • Examine his contacts.
It is necessary to inspect the boiler temperature sensor and connecting wires.
  1. Fan blades rotate too slowly (Bosch WBN 6000-24C).
  2. Short circuit of the pressure switch (Bosch ZWE 24-5 MFA, Bosch ZWE 24-4 (28-4), ZSE 24-4 MFA, Bosch ZSC 24-3 (35-3) MFA, ZWC 24-3 (28-3, 35-3) MFA).
  1. Check whether the mains voltage is sufficient. Clean the fan blades and smoke exhaust shaft.
  2. Check the pipes leading to the relay. Install the correct part.
- The fan rotates at low speed. You need to check the mains voltage. Also inspect the flue gas exhaust system and, if necessary, clean or repair it. The pressure switch does not work and does not open. Perform diagnostics and replace the element. When coding C6, additionally check the rotation of the fan.
- The differential pressure switch does not open if the fan is turned off. The differential needs to be inspected. pressure switch. The relay does not close.
- The differential pressure switch does not close. Check the fan and wires with plugs. Replace if necessary. Inspect the differential. pressure switch and exhaust pipes for combustion products. The fan is faulty. Reconnect the plug, repair the fan.
SE The pressure in the heating system has dropped. Open the water supply valve. Add water until the readings are normal.
CC/d5 The system “does not see” the external temperature sensor. Connect the cable more tightly and make sure that the part is in good condition.
CC Jumper 161 on ST8 is not fixed. If the jumper is in place, connect the plug correctly. Contact the service center.
It is necessary to inspect the sensor and Temperature difference exceeded. Carry out an inspection:
  • pump;
  • bypass.

Measure your blood pressure.

- There is not enough pressure in the heating system. Needs to be filled with water. The adjustment valve has failed. Carry out diagnostics of the valve and its wiring. If there is a malfunction, install a new part.
E0 There is a problem with the printed circuit board. Reconnect the contacts or install a working board.
E2 The supply line thermistor has failed. Check the element for open circuit or short circuit. Check the connectors for oxidation, clean and replace parts.
E9 (11) Signal from the heat exchanger temperature sensor. What to do? Check:
  • Connections and wires for breaks, damage, oxidation.
  • Pressure in the heating circuit. If it falls below the mark, turn on the recharge.
  • Thermal sensor short circuit, open.
  • Pump to block. Perform unlocking and repair.
  • Electronic control module.
  • Presence of air in the system. Bleed the air with Mayevsky's taps.

Clean the radiator from scale and dirt.

EA The flame in the burner went out. How to fix the problem:
  • Open the gas valve all the way.
  • If the pressure in the system decreases, contact your gas service.
  • Voltage drops in the network - if there are frequent surges, connect a stabilizer.
  • Tighten connections.
  • Clean the chimney from soot. Resume cravings.
  • Clean the ignition electrode, install it in its original place when displaced.
  • Diagnose the gas controller.
  • Inspect and, if found, remove deposits from the walls of the heat exchanger.
  • Call a specialist to check gas fittings and control board.
er Signal about failure of one of the nodes. Perform a full boiler diagnostic.
F0 Internal problem. Inspect and reconnect the terminals and wires to the control module. Make sure they are intact. If everything is ok, change the module.
Check the gas system, replace if necessary. The equipment is not functioning, but the flame is detected. Check if the chimney is working properly. Confirm the presence of traction. Perform diagnostics of sensors, electrodes, cables.
- When switched off, the boiler detects a flame. Check for oxidation of the electrodes and replace if necessary. The fuel supply is shut off, but there is a signal indicating the presence of a flame. Inspect the ionization electrode and the serviceability of the shut-off valves.
P Accidental key press on the panel. Press the same button and hold for 30 seconds.
| | The fan is not adjusted. Perform the adjustment.
F.A. The boiler type has not been determined. Set the type.
23 The fuel type is indicated.

Other faults

There are problems with “ ” boilers that are not displayed as an error.

The burner does not work

It is necessary to check the condition and turn on the emergency and starting switches. If one of the safety circuit breakers is faulty, repair it or replace it with a working device.

Also carry out diagnostics of temperature controllers and outlet product relays. Perform preventative cleaning of the firebox, burner, nozzles, and exhaust pipes.

No spark, no ignition

Look for the problem in:

  • Ignition electrode. Clean it and place it closer to the burner.
  • Burner.
  • Ignition transformer.

Noise and hum when the boiler is turned on

Clean the parts, including the heat exchanger, from scale. Salt deposits interfere with heat transfer, so the water boils and hisses. If the plaque is not removed, the unit will overheat and fail.

Hot water does not turn on

If there is no hot water when you open the faucet, inspect the three-way valve. If it breaks, it needs to be replaced. Also make sure that the mixer is in working order, clean the pipes and filters from blockages.

Whistle when igniting the burner

The size of the nozzles does not correspond to the pressure in the gas line. Change them.

Black smoke and soot

The ignition unit needs to be cleaned. Parts and holes are clogged with dust and dirt.

Popping noise when igniting

What could have happened:

  • The gas supply is set incorrectly.
  • Incorrect injector size.
  • The chimney is clogged.
  • Incorrect chimney shaft structure.
  • Ventilation in the room is poor.

We hope that after reading the article, you will determine the cause of the breakdown. You can carry out repairs yourself if you are technically savvy. However, remember: before starting work, be sure to turn off the gas and water supplies.

Bosch Gaz 6000 boiler errors

Error A7 - The hot water temperature sensor has a malfunction.

Error Ad - Boiler temperature sensor not detected.

Check the boiler sensor and connection wires.

Error C1 - The fan rotates at a low frequency.

Check the voltage in the network.

Check flue gas outlet. Clean or repair if necessary.

Error C4 - The differential pressure switch does not open when the fan is not working.

Check the differential. pressure switch.

Error C6 - The differential pressure switch does not close.

Check differential pressure switch, as well as flue gas exhaust pipes.

Error C7 - The fan is not functioning.

Check the fan, wire and plug. Replace if necessary.

Error CE - Low pressure to fill the heating system.

Add water.

Error d7 - There is a malfunction in the gas fittings of the Bosch 6000 wall-mounted boiler.

Check the connection wire.

Error E2 - Faulty or broken temperature sensor on the supply line.

Check the sensor for defects, as well as a possible short circuit in its wire. Replace if necessary.

Error E9 - The heat exchanger temperature limiter has tripped.

Check the heat exchanger temperature limiter for a defect, as well as a possible short circuit in its wire. Replace if necessary.

Check the operating pressure in the heating system.

Check the temperature limiter and replace it if necessary.

Check pump starting. If necessary, replace the pump.

Check the fuse, replace if necessary.

Remove air from the Bosch 6000 gas boiler.

Check the water circuit of the heat exchanger; if damaged, replace it.

Check the flue gas temperature limiter for a defect, as well as a possible short circuit in its wire. Replace if necessary.

EA Error - No flame found.

Check the connection of the protection wire.

Check the opening of the gas valve.

Check gas supply pressure. If necessary, correct the problem.

Check the connection to the electrical network.

Check the electrodes and wires. If necessary, correct the problem.

Check the flue gas outlet. Clean or repair if necessary.

Adjust the gas. If necessary, correct the problem.

For natural gas: check the gas flow control relay. If necessary, correct the problem.

When using a combustion air intake from a room, check the air draft into the room and the ventilation openings.

Clean the heat exchanger.

Inspect gas fittings. Replace if necessary.

Error codes for gas boilers Bosch ZSC / ZWC 24 MFA

A7 - Hot water temperature sensor is faulty.

Check for damage or short circuit of the temperature sensor and its wire, replace if necessary.

A8 - The connection to the BUS is interrupted.

Check connection cable and regulators.

A9 - Hot water temperature sensor is not installed correctly.

Check the installation area, if necessary, remove the sensor and reinstall it using heat-conducting paste.

Ad - Boiler sensor not detected.

Check the boiler sensor and connecting cable.

b1 - Coding plug not detected.

Insert the coding plug correctly, measure it and replace it if necessary.

C1 - During operation of the device, the differential pressure switch opened.

Check the differential pressure switch, exhaust device and connecting pipes.

C4 - The differential pressure switch does not open in the non-working position.

Check the differential pressure switch.

C6 - The differential pressure switch does not close.
Check the differential pressure switch and flue gas pipes.

d3 - Jumper 161 not detected on ST8

If there is a jumper, insert the plug correctly and check the external limiter. Otherwise: is there a jumper?

d4 - Temperature difference too large.

Check the pump, bypass hose and system pressure.

E2 - The flow temperature sensor does not work.

Check temperature sensor and connecting cable.

E9 - The limiter in the supply line has tripped.

Check the pressure in the system, temperature sensors, check the operation of the pumps and the fuse on the electronic board, remove air from the device.

EA - Bosch ZSC / ZWC boiler does not detect flame.

Is the gas valve open? Check the pressure in the gas network, the network connection, the starting electrode with cable and the ionization electrode with cable.

F0 - Internal fault.

Check the connection of the electrical plug contacts and start lines and, if necessary, replace the electronic board.

F7 - Although the boiler is turned off, a flame is detected.

Check electrodes and cable. If the flue gas exhaust works, check the electronic board for moisture.

FA - Flame detected after gas supply was turned off.

Check the ionization electrode. Check gas fittings.

Fd - The button was mistakenly pressed for too long (more than 30 seconds).

Press the button again for less than 30 seconds.

CC - Outside temperature sensor not detected.

Check the outside temperature sensor and connecting cable for damage.

Malfunctions of Bosch gas boilers

The burner does not turn on

Check the operation of the emergency switch of the heating system - If necessary, turn it on.

Check the operation of the control system start switch - If necessary, turn it on.

Inspect the safety circuit breakers - Check their functionality, if necessary, replace the faulty circuit breaker.

Inspect the boiler water temperature regulator - Check and, if necessary, replace the faulty part.

The safety temperature limiter is faulty - Check and replace the part if necessary.

An error message appears from external safety devices (e.g. water quantity control safety device) - Check heating system, eliminate errors, replace the faulty device if necessary.

The flue gas monitoring relay is activated - AW 10: unlock the flue gas monitoring relay. AW 50: Wait a maximum of 15 minutes.

The Bosch boiler will turn on automatically if there is a request for heat. If it is triggered repeatedly, check the flue gas path and the functionality of the flue gas monitoring relay. Replace the relay if it is faulty.

The burner lights up and turns off due to a malfunction. No pilot spark

There is a sound of ignition spark formation when the ignition cable is removed - If not: replace the ignition transformer.

If yes: Replace the ignition electrode or ignition burner.

The burner lights up and turns off due to a malfunction

Is the gas valve open? - Open the gas tap.

Natural gas supply pressure is higher than 8 mbar - If not: determine the cause and correct the fault.

Has air been removed from the gas pipeline? - Vent the air until the gas can be ignited.

The burner lights up and turns off due to a malfunction. No ionization current

The N and L connections may be reversed - Correct the error.

Check the voltage between L and PE - If there is no voltage: ground PE, install an isolation transformer if necessary.

Poor contact of the ionization wire - Eliminate the error, replace the defective part if necessary.

The ionization electrode is shorted to ground - The burner control is faulty.

Boiling sounds

Are there lime deposits or scale formation in the Bosch boiler?

Clean the boiler water circuit in accordance with the manufacturer's recommendations.

If there is constant water loss, determine and eliminate the cause.

If necessary, carry out water treatment and install a dirt trap.

Flat main flame

Are the injectors suitable for the supplied gas? - If not: install the correct injectors.

Matching holes supply and exhaust ventilation local rules and requirements for the installation of gas equipment?

If there is insufficient air flow, the deficiency must be corrected immediately.

Sharp whistle of the burner

Is it installed correct pressure on the injectors? - Check the set value, correct if necessary.

The burner is smoking

Is there any noticeable dirt in or below the cracks of the burner rods? - Carry out wet cleaning of the burner as described in these instructions.

Find the source of contamination and protect against further contamination.

Are the air supply and exhaust openings always operational? - Are there deposits or fibrous contamination on the surface of the heat exchanger?

Inspect through the cleaning holes and combustion chamber. Carry out dry and, if necessary, wet cleaning of the boiler as described in this manual.

Are the burner rods damaged or deformed, are there any deformation of individual slots? - Replace the burner rods, determine and eliminate the cause of the malfunction.

Information: Damage or deformation only occurs if at least one of the above faults occurs.

The burner ignites very loudly, with strong combustion noises, flames are visible on the nozzles

Are the correct injectors installed? - Switch off the burner, install a new burner rod and correct the incorrect gas type setting.

Are the injector pressures set to the correct pressure? - The smell of flue gases in the room where the boiler is installed.

Are flue gases coming out of the draft breaker? - Determine the cause of improper flue gas removal and correct the problem.

If it is not possible to eliminate the cause immediately, then you need to turn off the burner.

Vacuum in chimney more than 3 Pa? Blockage in the flue gas path?

Are the chimney dimensions calculated correctly?

Do they work in the boiler room? exhaust fans that remove air from the room?