Standard characteristics of the water heating boiler PTVM 120. Water heating boiler PTVM - technical characteristics. The procedure for ordering automation or a full range of works for the technical re-equipment of boilers of the “ptvm” series

PTVM boilers with capacity: 30; 50; 100 MW.

Water heating boilers PTVM are intended for installation in heating boiler houses as the main source of heat supply to obtain hot water temperature 150°C, used in heating systems, hot water supply of industrial and household use and at the thermal power plant.

Technical characteristics of PTVM-30 boilers

The boiler is a direct-flow boiler with a U-shaped closed arrangement of heating surfaces. The boiler furnace is completely shielded by pipes 060x3 mm, located with a pitch of S = 64 mm, and is equipped with six gas-oil burners MGMG-6, installed counter-clockwise on the side walls.

Convective heating surfaces are located in a convective flue with side walls, shielded pipes 083x3.5 mm, which are risers of convective sections made of pipes 028x3 mm. The rear wall of the convective flue is shielded with 60x3 mm pipes. The pipe system of the PTVM-30 boiler rests on a frame frame at an elevation of 5.14 m.

The range of boiler load regulation is 30 -100% of the nominal output. The heating output of the boiler is changed by changing the number of operating burners. The water flow through the boiler must be maintained constant; when the heat load changes, the difference in temperature of the water at the inlet and outlet of the boiler changes.

By agreement, boilers can be equipped with any foreign or domestic gas burners corresponding performance.

Boilers operating on fuel oil can be equipped with a gas pulse cleaning device (GCP) to remove external deposits from the pipes of convective heating surfaces.

Specifications

PTVM-30

Type of fuel

Gas/fuel oil

Water pressure at the boiler inlet, no more than, MPa

Inlet water temperature, °C

Thermal insulation control range relative to the nominal value, %

Water consumption, t/h

Fuel consumption, m/h-gas/kg/h-fuel oil

Flue gas temperature, °C, gas/fuel oil

Full assigned service life, years, not less

Boiler efficiency, %, not less, gas/fuel oil

It is possible to manufacture a boiler for a pressure of 2.5

Technical characteristics of boilers PTVM-50 and PTVM-100

Boilers PTVM-50 and PTVM-100 can be operated both in main mode and in peak mode (for heating network water), respectively, from 70 to 150°C and from 110 to 150°C.

The boilers have a tower layout: a convective heating surface is located above the vertical combustion chamber. The combustion chamber is screened with pipes 060x3 mm. The convective heating surface of the PTVM-100 boilers consists of eight packages, and the PTVM-50 boiler consists of four packages. It is assembled from U-shaped screens from pipes 028x3 mm. The side walls of the convective flue are closed with pipes 083x3.5 with a pitch of 128 mm and are also risers for convective half-sections. The boiler pipe systems are suspended from the frame by the upper manifolds and freely expand downwards.

The PTVM-50 boiler is equipped with 12 MGMG-6 gas and oil burners - six on each side. The PTVM-100 boiler is equipped with 16 MGMG-8 gas and oil burners - eight on each side. Each burner is equipped with an individual blower fan. By agreement, boilers can be equipped with any foreign or domestic gas burners of appropriate capacity.

Boilers operating on fuel oil can be equipped with a gas pulse cleaning device (GCP) to remove external deposits from the pipes of convective heating surfaces.

The boilers have lightweight pipe lining and thermal insulation and are supplied without casing. Masonry and insulating materials are not included in the delivery package.

Specifications

PTVM-50

PTVM-100

Nominal heating capacity, MW (Gcal/h)

Type of fuel

Water pressure at the boiler inlet, no more than, MPa

Water pressure at the boiler outlet, not less, MPa

Inlet water temperature, °C (main/peak)

Outlet water temperature, °C

Hydraulic resistance, MPa

Range of regulation of heating capacity in relation to the nominal,%

Technical description of the water heating boiler PTVM-30M

The gas-oil hot water boiler is intended for installation in heating boiler houses as the main source of heat supply to produce hot water at a temperature of 150 °C, used in heating systems, hot water supply for industrial and domestic purposes.

The boiler is a direct-flow boiler with a U-shaped closed arrangement of heating surfaces. The boiler furnace is completely shielded by pipes Ø60x3 mm, located with a pitch of S=64 mm, and is equipped with six oil-gas burners MGMG-6, installed oppositely on the side walls.

Convective heating surfaces located in a convective flue with side walls, shielded pipes Ø83x3.5 mm, which are risers of convective sections made of pipes Ø28x3 mm. The rear wall of the convective flue is shielded with pipes Ø60x3 mm.

Pipe system of the boiler PTVM-30M rests on the frame frame at 5.14 m.

Load control range boilers% of rated output. The heating output of the boiler is changed by changing the number of operating burners.

Water flow through the boiler must be maintained constant; when the heat load changes, the temperature difference between the water at the inlet and outlet of the boiler changes.

Oil fired boilers, can be equipped with a gas-pulse cleaning device (GCP) to remove external deposits from convective surface pipes for heating.

Technical description of hot water boilers PTVM-50, PTVM-100, PTVM-120

Hot water boilers are designed to produce hot water at a temperature of 150 °C in free-standing boiler houses, used in heating systems, hot water supply for industrial and domestic purposes and at thermal power plants.

Boilers PTVM-50 and PTVM-100 can be operated both in main mode and in peak mode (for heating network water), respectively, from 70 to 150 °C and from 110 to 150 °C.

The boilers have a tower layout: a convective heating surface is located above the vertical combustion chamber. The combustion chamber is shielded with pipes Ø60x3 mm.

Convective heating surface of PTVM-100 and PTVM-120 boilers consists of eight packages, and boiler PTVM-50- from four packages, assembled from U-shaped screens from pipes Ø28x3 mm. The side walls of the convective flue are covered with pipes Ø83x3.5 with a pitch of 128 mm and are also risers for convective half-sections.

Boiler tube systems suspended from the frame by the upper collectors and freely expand downwards.

Boiler PTVM-50 equipped with 12 gas and oil burners MGMG-6 - six on each side.

Boiler PTVM-100

Boiler PTVM-120 equipped with 16 gas and oil burners MGMG-8 - eight on each side.

Each burner is equipped with an individual blower fan.

By agreement, boilers can also be equipped with foreign and domestic gas burners of appropriate performance (having the necessary specifications, certificate of conformity and permission to use Rostechnadzor).

Maintenance of the burner device, its description and technical characteristics are given in the documentation supplied with the burner devices.

The boilers have lightweight lining and thermal insulation.

https://pandia.ru/text/78/369/images/image006_45.jpg" alt="Water heating boiler PTVM-50" width="400" height="469">.jpg" alt="Technical characteristics of the PTVM-180 boiler" width="800" height="356">!}

Boilers PTVM-120 (KV-GM-139.6-150) have a tower layout: above a vertical combustion chamber rectangular shape the convective heating surface is located.

The combustion chamber is screened with pipes Ø60x3 mm with a pitch of 64 mm and is divided in two by a double-light screen made of pipes Ø60x3 mm with a pitch.

The convective heating surface of the PTVM-120 (KV-GM-139.6-150) boilers consists of eight packages, assembled from U-shaped screens from 28x3 mm pipes. The side walls of the convective flue are covered with pipes 83x3.5 mm, with a pitch of 128 mm, and are also risers for convective half-sections.

The pipe systems of the PTVM-120 (KV-GM-139.6-150) boilers are suspended from the frame by the upper collectors and expanded downward.

The design of the PTVM-120 (KV-GM-139.6-150) boilers allows semi-open installation - only the lower part of the boiler is enclosed in the room, where the burners, fittings, automation and blower fans are located, which significantly reduces the cost of constructing the heating station building and creates conveniences for summer repairs.

For boilers PTVM-120 (KV-GM-139.6-150) it is possible to install them both with steel chimney, directly resting on the boiler frame, or with a free-standing reinforced concrete or brick chimney.

The PTVM-120 (KV-GM-139.6-150) boilers are equipped with sixteen MGMG-8 gas and oil burners, located in pairs on the front and back walls eight pieces on each side. Each burner is equipped with an individual blower fan.

By agreement with Biysk Boiler Plant OJSC, PTVM-120 (KV-GM-139.6-150) boilers can also be equipped with foreign and domestic gas burners of appropriate capacity.

To clean the convective part of PTVM-120 (KV-GM-139.6-150) boilers, it is washed with network water using special nozzle-type nozzles. Water consumption depends on the boiler operating mode: in winter period A 4-way water circulation scheme is used, in summer period- two-way (peak). With a 4-pass scheme, water from the heating network is supplied to one lower collector and sequentially passes through all elements of the heating surface of the boiler, performing lifting and lowering movements, after which it is discharged through the lower collector to heating network. In a two-pass mode, water enters simultaneously into two lower collectors and, when heated, is removed into the heating network. In this case, almost twice as much water is passed through, because it enters the boiler with more high temperature: 110°C instead of 70°C.

PTVM-120 (KV-GM-139.6-150) boilers have lightweight lining and frame thermal insulation. Masonry and insulating materials are not included in the plant’s supply.